Key takeaways
- The H200 NVL bridge runs at 900 GB/s across two cards or 1,800 GB/s across four. Bridges are separate parts, so check which one a quote includes.
- An eight-card H200 NVL server is two four-way NVLink islands, not one eight-way domain. TP=4 stays on NVLink, TP=8 does not.
- No Blackwell PCIe card takes an NVLink bridge. The B200 is SXM only and the RTX PRO 6000 Blackwell has no NVLink, so Hopper is currently the only route to a bridged island in a PCIe server.
- All three PCIe options here are air-coolable at eight GPUs per 4U, but fitting H200 NVL drops the Dell XE7745's ambient ceiling from 35°C to 30°C.
- Above eight GPUs the choice closes, because rack-scale Blackwell is liquid only.
An H200 NVL on a four-slot NVLink bridge pools 564 GB of HBM3e across four cards at 1,800 GB/s. The same card on a two-slot bridge pools 282 GB at 900 GB/s. A PCIe card with no bridge reaches its neighbours at 128 GB/s over PCIe Gen5. Those three numbers are the SXM vs NVL vs PCIe decision, and two questions settle which one applies to you.
The form factor question gets asked as a performance question. Most of it is a facility question.
We supply H200 NVL and RTX PRO 6000 Blackwell direct. If you already know your GPU count and parallelism strategy, request H200 NVL pricing and skip to a real configuration.
Does one model have to span more than one GPU?
If not, the interconnect tables are irrelevant to you. You are running replicas, or models that fit in one card, and the GPU-to-GPU link sits idle. Buy on memory per card, price, and what your chassis will take.
The RTX PRO 6000 Blackwell Server Edition is the card for that work: 96 GB of GDDR7 on a 512-bit bus at 1,597 GB/s, up to 600 W configurable, PCIe Gen5 x16, and MIG up to four isolated instances at 24 GB each, per NVIDIA's datasheet. Passive cooling. The DisplayPort connectors are physically present and disabled on the Server Edition.
If one model does have to span GPUs, a single number decides the rest.
How many GPUs need to sit in one NVLink domain?
Two or four, and a bridged PCIe card covers it. Eight, and you need SXM on an HGX baseboard. Seventy-two, and you are buying a liquid-cooled rack.
NVLink is a scale-up fabric. It connects GPUs inside a box so that tensor-parallel traffic never touches PCIe. InfiniBand and Ethernet are scale-out, connecting boxes to each other. They are not substitutes for each other, and a multi-node cluster needs both.
| RTX PRO 6000 Blackwell SE | H100 NVL | H200 NVL | H200 SXM | B200 SXM | |
|---|---|---|---|---|---|
| Form factor | PCIe, dual slot FHFL | PCIe, dual slot FHFL | PCIe, dual slot FHFL | SXM5 on HGX board | SXM6 on HGX board |
| Memory | 96 GB GDDR7 | 94 GB HBM3 | 141 GB HBM3e | 141 GB HBM3e | 180 GB HBM3e |
| Bandwidth | 1,597 GB/s | 3.9 TB/s | 4,813 GB/s | 4.8 TB/s | Up to 8 TB/s |
| NVLink | None | 600 GB/s | 900 GB/s two-way, 1,800 GB/s four-way | 900 GB/s via NVSwitch | 1.8 TB/s via NVSwitch |
| Largest NVLink domain | 1 GPU | 2 GPUs | 4 GPUs | 8 GPUs | 8 GPUs, or 72 on NVL72 |
| Power | Up to 600 W configurable | 350 to 400 W configurable | Up to 600 W, 350 W compliance limit, 200 W floor | Up to 700 W | 1000 W |
| Cooling | Air, passive card | Air, passive card | Air, passive card | Air or liquid | Air or liquid, chassis dependent |
| MIG | Up to 4 at 24 GB | Up to 7 at 12 GB | Up to 7 | Up to 7 | Up to 7 |
| Buy standalone? | Yes | Yes | Yes | No, HGX board only | No, HGX board only |
The last row is the one most buyers do not know, and it belongs in the table. The three PCIe columns come from NVIDIA datasheets and the H200 NVL product brief. The two SXM columns are confirmed against NVIDIA's own documentation: the H200 product page gives the SXM card up to 700 W configurable against the NVL card's 600 W, and NVIDIA's HGX reference architecture gives the B200 up to 8 TB/s of bandwidth across 180 GB of HBM3e.
What the NVLink bridge on the H200 buys you
The H200 NVL is a full-height, full-length, dual-slot PCIe card carrying 141 GB of HBM3e at 4,813 GB/s. One wide bridge sits along the top edge. The two-slot bridge spans two cards at 900 GB/s, and the four-slot bridge spans four at 1,800 GB/s.
NVIDIA's reference architecture blog puts the four-way pool at 564 GB of HBM3e, three times the H100 NVL's 188 GB two-way pool, with up to 1.7x faster LLM inference and 1.3x more HPC performance than the H100 NVL.
Why eight cards is not an eight-way domain
An eight-GPU H200 NVL server runs as two four-way islands, and the islands reach each other over PCIe. Dell's XE7745 configuration rules require four or eight GPUs for the four-way bridge. The product brief tightens things further: bridge inside one CPU domain, keep the GPU count a power of two, keep an even number of GPUs per socket, and match bridge spans across sockets. Bridging across CPUs is listed as allowed and not recommended.
TP=4 stays inside NVLink on this card. TP=8 does not. That is our reading of the topology rather than an NVIDIA statement, though the bridging rules leave little else to conclude. If your serving stack is pinned to eight-way tensor parallelism, buy SXM.
Not sure whether your parallelism strategy fits inside a four-way island?
Talk to us about a configuration →What it costs when traffic crosses PCIe
Less is published here than you would expect. The one measurement we found arrived through a hardware wiki citing CloudRift benchmarks rather than from CloudRift directly.
H200 vs H100 NVL: what changed
Memory is the headline. NVIDIA's H100 NVL datasheet gives 94 GB at 3.9 TB/s against the H200 NVL's 141 GB at 4,813 GB/s. Compute is the same silicon.
Topology is the more useful change. The H100 NVL bridges exactly two cards at 600 GB/s. The H200 NVL bridges two or four. Moving between them gets you more memory per card and the first bridged PCIe part with a four-GPU island.
Power moves against you while you do it. The H100 NVL is 350 to 400 W configurable. The H200 NVL defaults to a 600 W maximum, with a 350 W power-compliance limit and a 200 W floor. Swapping eight H100 NVL cards for eight H200 NVL adds up to 1.6 kW inside one 4U chassis.
Blackwell took the bridge away
No Blackwell PCIe card takes an NVLink bridge. The B200 ships in SXM6 only, stated in Lenovo's product guide: "The NVIDIA B200 180GB 1000W GPU is offered in the SXM6 form factor." There is no standalone B200 card to buy. NVIDIA's PCIe Blackwell part is the RTX PRO 6000 Blackwell, and it has no NVLink on any edition. Boston Labs' spec table lists "NVLink (SLI): No" for both Workstation editions, and NVIDIA's Server Edition datasheet carries no NVLink row.
Hopper is therefore the only generation currently offering an NVLink island inside a PCIe server. Whether NVIDIA ships a bridged Blackwell or Rubin card later, we have no idea. What holds today is that the H200 NVL has no successor in its own form factor.
Two products, same two letters
"NVL" means a bridged PCIe card on the H100 NVL and H200 NVL. On GB200 NVL72 and GB300 NVL72 it means a rack-scale NVLink domain of 72 GPUs. Vendor pages move between the two without saying so.
Can you run this in an air-cooled GPU rack?
Usually, and the derate catches people.
NVIDIA positions the H200 NVL for "lower-power, air-cooled rack designs". The card is passively cooled, so system airflow does the work, and the heat sink accepts air from either direction. Ambient range is 10 to 45°C.
Read the chassis spec, not the card spec
The Dell XE7745 is 4U, air-cooled, and takes eight double-wide PCIe Gen5 GPUs at up to 600 W each. Its ambient limit is 35°C, dropping to 30°C once you fit H200 NVL, RTX PRO 6000 or 256 GB DIMMs. The dense build costs five degrees of headroom. If your hall runs warm in July, that is the number that decides your summer.
Lenovo sells the cap as a line item. Its RTX PRO 6000 Server Edition listing includes feature code CHWT, "Slot Capped at 450W", alongside the full-power CBK8. An OEM shipping a 450 W version of a 600 W card tells you what some chassis sustain in practice.
Tell us your hall's inlet temperature and rack feed when you ask for a price — we will size the configuration against those, not datasheet maximums.
Request H200 NVL pricing →Rack feed is the real limit
Eight cards at 600 W is 4.8 kW of GPU inside 4U, before CPUs, 24 DIMMs and fans. Dell fits that chassis with up to eight 3200 W Titanium supplies in 4+4 redundancy, giving 12.8 kW of live supply capacity per server. That arithmetic is ours rather than a published figure. Three servers like that and a single rack is carrying real load, so the question for your facility is what the rack feed delivers and at what inlet temperature, not whether air can cool the card.
Above eight-GPU boxes the choice disappears, because liquid is mandatory on rack-scale Blackwell. At eight GPUs it is still a choice: Lenovo air-cools HGX B200 in the SR680a V3 and water-cools the same board in the SR780a V3.
Put two things on the bill of materials early. Bridge kits are separate parts and they go out of stock, with an HPE two-way bridge listed at $1,131.99 and a PNY four-way kit at $1,504.00, the latter showing none in stock, both US resellers in early November 2026. And the RTX PRO 6000 Blackwell carries Lenovo's "Controlled" designation, so it is not sold into certain markets as determined by the US Government. Check that against your deployment region.
SXM vs NVL vs PCIe: the decision in four lines
One model per GPU, or models under 96 GB: plain PCIe. RTX PRO 6000 Blackwell, eight to a 4U box, air-cooled.
Two to four GPUs in one memory domain: H200 NVL with the four-slot bridge. 564 GB pooled, air-coolable, and the only current route to a bridged island.
Eight-way tensor parallelism: SXM on HGX, with the power and chassis constraints that follow.
Frontier-scale training: NVL72 class, liquid, and a different conversation.
Get a configuration that your facility can cool
We supply H200 NVL and RTX PRO 6000 Blackwell direct, which means we end up discussing inlet temperatures and rack feeds more often than bandwidth tables.
Request H200 NVL pricing — send your GPU count and target parallelism strategy. You will get a real lead time and a configuration your facility can actually cool, not a quote that falls over at the ambient derate.
Frequently asked questions
Can you air-cool an H200 NVL?
Does an eight-GPU H200 NVL server give you one eight-way NVLink domain?
Is there a B200 PCIe card?
Does the RTX PRO 6000 Blackwell support NVLink?
What is the difference between the H100 NVL and the H200 NVL?
Is the NVLink bridge included with the cards?